Reduced-Pressure Zone Backflow Preventers

Overview

Reduced-Pressure Zone Backflow Preventers protect municipal water systems from contamination by maintaining a minimum 2.0 psi differential between inlet and outlet pressures through two independent check valves and a relief valve assembly. The device creates a reduced-pressure zone that automatically discharges to atmosphere when backflow conditions occur, preventing cross-connections from industrial users or contaminated distribution lines from compromising potable water quality. RPZ assemblies typically achieve 99.9% backflow prevention effectiveness in municipal applications ranging from 0.75" to 20" line sizes. However, they require annual testing, generate continuous discharge during normal operation, and cause 8-15 psi pressure loss across the assembly.

Common Applications

• Service Water Lines to Chemical Feed Systems: RPZ assemblies protect potable water supplies from contamination by chemical feed solutions (chlorine, fluoride, coagulants). Installed upstream of chemical metering pumps with isolation valves on both sides. Selected for high-hazard protection where backpressure or backsiphonage could introduce toxic chemicals into distribution systems.

• Fire Protection System Connections: Municipal plants use RPZ devices where fire suppression systems connect to potable water mains. Prevents contaminated water from sprinkler systems, foam concentrates, or stagnant fire lines from entering drinking water supplies. Typically 4-8 inch assemblies with OS&Y gate valves upstream/downstream.

• Laboratory and Washdown Station Supplies: Protects potable water feeding plant laboratories, sample preparation areas, and equipment washdown stations. Prevents backflow of contaminated samples, cleaning chemicals, or wastewater from entering plant service water. Usually 1-2 inch assemblies with ball valve isolation.

• Auxiliary Equipment Cooling Water: RPZ assemblies protect service water lines supplying cooling water to pumps, compressors, and HVAC systems where antifreeze, corrosion inhibitors, or process contamination could backflow into potable supplies.

Operator Experience

Daily Operations: Operators visually inspect RPZ assemblies during routine rounds, checking for relief valve discharge indicating system backpressure or check valve failure. No routine adjustments required during normal operation. Pressure gauges on test ports (when installed) should show proper differential pressures: supply pressure, reduced zone pressure 2+ psi lower, and outlet pressure.

Maintenance: Annual testing required per AWWA standards using certified backflow tester with calibrated differential pressure gauge kit. Quarterly visual inspections for leaks, corrosion, or relief valve weeping. Rebuilding check valves and relief valves every 3-5 years depending on water quality. Requires confined space procedures if installed in vaults. Basic plumbing skills sufficient for valve maintenance.

Troubleshooting: Relief valve continuous discharge indicates failed downstream check valve or excessive system backpressure - requires immediate attention and water supply isolation. Reduced flow rates suggest fouled check valve seats or undersized assembly. Typical service life 15-20 years for quality bronze/stainless assemblies. Premature failure often caused by water

Major Components

• Inlet Shutoff Valve: Full-port ball or gate valve providing positive isolation upstream of assembly. Bronze or stainless steel construction for 1-2 inch sizes, iron body for 3 inch and larger. Must be fully open during operation to prevent pressure drop affecting assembly function.

• First Check Valve: Spring-loaded check valve preventing reverse flow from zone chamber into supply line. Bronze or stainless internals with replaceable elastomer seats. Sized for 2-5 psi pressure drop at design flow rates.

• Relief Valve: Differential pressure-operated valve maintaining 2 psi minimum pressure differential between supply and zone chamber. Opens to atmosphere when backpressure occurs, creating visible discharge. Stainless steel spring and seat materials for longevity.

• Second Check Valve: Downstream check valve preventing backflow from system into reduced pressure zone. Similar construction to first check but operates under lower differential pressure conditions.

• Outlet Shutoff Valve: Isolation valve downstream of assembly, typically same construction as inlet valve. Test ports located between components allow field testing of each check valve and relief valve independently.

Design Criteria

• Flow Rate Sizing: Size RPZ assemblies for maximum demand flow plus 10-15% safety factor. Typical municipal sizes range from 2" (50-200 GPM) to 12" (3,000-8,000 GPM). Velocity through device should not exceed 10 fps to minimize head loss.

• Pressure Requirements: Minimum upstream pressure of 30 psi required for proper operation. Typical head loss ranges from 12-25 psi depending on size and flow rate. Maximum working pressure typically 175-300 psi depending on model.

• Relief Valve Discharge: Relief valve must discharge continuously when differential pressure drops below 2 psi. Size discharge piping minimum one size larger than relief valve outlet. Discharge rate typically 1-5 GPM during normal operation.

• Installation Clearances: Minimum 12" clearance above highest point for testing/maintenance. Horizontal installations require 5x pipe diameter upstream, 2x downstream for proper flow conditioning.

• Testing Ports: 1/4" test cocks required on both sides of each check valve and relief valve chamber. Pressure differential across first check valve must be minimum 2 psi greater than across relief valve.

Key Design Decisions

• What is the required flow capacity and does it justify RPZ selection over double-check? Municipal applications above 2" typically require RPZ for high-hazard cross-connections. Undersizing results in excessive pressure loss (>25 psi) affecting system performance. Need: peak demand analysis, hazard assessment per AWWA M14.

• Can the system maintain minimum 30 psi upstream pressure under all flow conditions? Insufficient upstream pressure causes relief valve weeping, water waste, and potential backflow. Systems with marginal pressure may require booster pumps or pressure-sustaining valves. Need: hydraulic analysis, pump curves, system head calculations.

• Where will relief valve discharge be directed and is drainage adequate? Relief valve discharge of 1-5 GPM continuous flow plus potential full-flow discharge during testing requires proper drainage. Inadequate drainage causes flooding, foundation damage, or freezing issues. Need: site drainage survey, local codes, freeze protection requirements.

• What testing/maintenance access is required and available? Annual testing requires technician access to test ports and relief valve. Confined spaces or inadequate clearances prevent proper testing, creating liability issues. Need: site survey, maintenance procedures, accessibility requirements per local codes.

Specification Section

• Division 40 - Process Integration

• Section 40 05 23 - Backflow Prevention Assemblies

• Primary section for RPZ devices in water treatment applications. May also reference Division 22 (Plumbing) Section 22 11 19 for building service applications.

Submittal + Construction Considerations

• Material/Equipment Verification: Verify NSF/ANSI 61 certification for potable water contact, Confirm ASSE 1013 listing and local code compliance, Check pressure rating matches system conditions

• Installation Requirements: Minimum 12" clearances all sides for testing access, Proper drainage for relief valve discharge (6" minimum pipe), Freeze protection in cold climates

• Field Challenges: Inadequate test cock clearances discovered during installation, Relief valve drainage conflicts with site constraints

• Coordination Issues: Early coordination with testing contractor for access requirements, Lead times typically 4-6 weeks for standard sizes

Popular Manufacturers and Models

• Watts (Series 909) - Dominant in municipal market with bronze and stainless options

• Zurn Wilkins (Model 375) - Strong contractor relationships, reliable performance record

• Febco (Series 860) - Cost-effective option, popular in smaller municipalities

• Ames (Series 4000) - Heavy-duty designs for high-pressure applications

• All offer 2"-12" sizes typical for municipal service connections and booster pump protection.

Alternative Equipment

• Double Check Valve Assemblies - Lower cost ($800 vs $1,500 for 4" units), acceptable for non-health hazard cross-connections, but prohibited for high-hazard applications.

• Air Gap Separation - Absolute protection but requires break tanks, booster pumps, and significant space/cost.

• Pressure Vacuum Breakers - Atmospheric types limited to non-continuous pressure applications, spill-resistant models cost 30% less than RPZ for irrigation connections.

Real-World Tips

Oversizing is common mistake - specify based on actual demand, not pipe size. 4" RPZ often adequate where 6" service exists. Maintain manufacturer relationships for technical support during commissioning issues. Group multiple devices in mechanical rooms when possible to reduce installation costs and simplify testing access. Consider stainless steel internals in aggressive water chemistry areas to extend service life beyond standard 5-year rebuild cycle.

Connect with Local Representative
If you need help with sizing, system compatibility,  maintenance planning, or sourcing, connect with your local manufacturer's representative. They can assist you in selecting the right equipment for your specific application and site conditions.

Connect with a Local Distributor

If you need help with sizing, system compatibility,  maintenance planning, or sourcing, connect with your local manufacturer's representative. They can assist you in selecting the right equipment for your specific application and site conditions.